> Line Post Insulators
(ANSI) |
| |
| Cat. No. |
4011 |
4013 |
4015 |
4017 |
4019 |
| Fig. |
1 |
1 |
1 |
1 |
1 |
| Class ANSI |
57-11 |
57-12 |
57-13 |
57-14 |
57-15 |
Main Dimensions
(mm) |
H |
254 |
330 |
419 |
495 |
571 |
| D |
152 |
165 |
171 |
184 |
190 |
| R1 |
- |
- |
- |
- |
- |
| R2 |
- |
- |
- |
- |
- |
| H1 |
- |
- |
- |
- |
- |
| H2 |
- |
- |
- |
- |
- |
| d |
102 |
102 |
102 |
102 |
102 |
| Nominal Voltage (kV) |
- |
- |
- |
- |
- |
| Creepage Distance (mm) |
355 |
558 |
736 |
1016 |
1143 |
| Dry Arcing Distance (mm) |
165 |
241 |
311 |
368 |
438 |
| Cantilever Strength (kN) |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
| Critical Impulse Flashover Voltage |
Positive (kV) |
130 |
180 |
210 |
255 |
290 |
| Negative (kV) |
155 |
205 |
260 |
340 |
380 |
| Power-frequency Withstand Voltage |
Dry (kV) |
- |
- |
- |
- |
- |
| Wet (kV) |
- |
- |
- |
- |
- |
| Power-frequency Flashover Voltage |
Dry (kV) |
80 |
110 |
125 |
150 |
175 |
| Wet (kV) |
60 |
85 |
100 |
125 |
150 |
| Lighting Impulse Withstand Voltage
(kV) |
- |
- |
- |
- |
- |
| Test Voltage to Ground (kV) |
15 |
22 |
30 |
44 |
44 |
| Maximum RIV at 1000kHz (uV) |
100 |
100 |
200 |
200 |
200 |
| Quantity of Shed |
4 |
6 |
8 |
10 |
12 |
| Weight (kg) |
- |
- |
- |
- |
- |
| Fired Blank: White Glazed |
|